Which instrument setting does the source describe?

NI defines sample rate as the rate at which an analog-to-digital converter turns the input waveform into digital data. Its tutorial separately discusses input bandwidth and aliasing. These properties concern acquisition; a row timestamp in a trend export does not document all of them.

Commissioning Docs is independent and is not affiliated with NI. Use the actual instrument and historian manuals to establish how a recorded value was acquired and reduced. This worksheet does not choose a sample rate, approve a measurement chain or specify a commissioning acceptance limit.

Sources: NI: NI: Acquiring an Analog Signal, updated 3 September 2026

Which evidence belongs beside a trend file?

Keep each channel tied to the approved test requirement and equipment identifier. Obtain the actual configuration and export definition rather than infer the processing chain from a graph that looks smooth.

Which evidence belongs beside a trend file?
Evidence fieldWhat to recordWhat it cannot establish alone
AcquisitionRate, instrument function and channelHistorian storage behavior
Input processingRelevant bandwidth and filter referenceAdequacy for every event
AggregationMean, maximum, last value or other stated ruleThe original waveform
WindowDuration and timestamp conventionClock alignment with other sources
Saved intervalSpacing and gaps in retained rowsAcquisition sample rate
Raw evidenceWhether and where raw samples are retainedA retrospective reconstruction if absent

How can equal logging intervals preserve different information?

Illustrative example. A fictional minute contains 60 equally weighted, already acquired one-second values. Fifty-nine are zero and one is 60 signal units. A minute mean is 60 / 60 = 1 signal unit, while a minute maximum is 60. Both files can contain one row per minute and still describe different summaries.

This arithmetic is not a simulated meter, waveform or electrical test. It does not establish that the one-second acquisition captured an actual transient. A saved average of 1 cannot be expanded into the missing original sequence, and a saved maximum does not reveal its duration or shape.

How should an evidence limitation be closed?

Ask the commissioning professional to assess whether the retained processing and timing meet the actual test requirement. Preserve the original file, configuration reference and any limitation. Do not fill missing raw samples with interpolated values labeled as measurements.

If additional evidence is required, follow the authorized test and safety process. This site prepares documentation and does not perform testing. Engineering sign-off is performed only by the registered engineer on the job.

Common questions

What else should the bid team know?

Is one row per minute proof of one sample per minute?

No. The saved interval and acquisition rate are separate settings.

Can a minute average recreate a short peak?

No. Obtain the actual retained evidence and processing definition.

Does this worksheet prescribe a safe sample rate?

No. The responsible technical reviewer decides the required measurement chain.

Primary sources

  1. NI: Acquiring an Analog Signal, updated 3 September 2026NI